Wire Size & Amp Ratings
- Ampacity is the maximum current that a conductor can carry continuously under the conditions of use without exceeding its temperature rating. Current is measured in amperes or “amps”. You must use the correct size wire for the current (load) requirement of the circuit to prevent the wire from overheating.
- The number and type of electrical devices connected to a circuit determine the ampacity requirement of the conductor. Usually, a general purpose house circuit is designed for 20 amps. Lighting circuits may be designed for only 15 amps
- To calculate the load requirement for a circuit, first add up the wattage of all the electrical devices that will be on the circuit. Then, divide the total wattage by the voltage of the system, typically 120 or 240, and that will give you the required current or amps.
2.6 As A Fraction
Copper | Aluminum | ||||
---|---|---|---|---|---|
Wire Gauge Size | 60°C (140°F) NM-B, UF-B | 75°C (167°F) THW, THWN, SE, USE, XHHW | 90°C (194°F) THWN-2, THHN, XHHW-2, USE-2 | 75°C (167°F) THW, THWN, SE, USE, XHHW | 90°C (194°F) XHHW-2, THHN, THWN-2 |
14 | 15 | 20 | 25 | --- | --- |
12 | 20 | 25 | 30 | 20 | 25 |
10 | 30 | 35 | 40 | 30 | 35 |
8 | 40 | 50 | 55 | 40 | 45 |
6 | 55 | 65 | 75 | 50 | 55 |
4 | 70 | 85 | 95 | 65 | 75 |
3 | 85 | 100 | 115 | 75 | 85 |
2 | 95 | 115 | 130 | 90 | 100 |
1 | --- | 130 | 145 | 100 | 115 |
1/0 | --- | 150 | 170 | 120 | 135 |
2/0 | --- | 175 | 195 | 135 | 150 |
3/0 | --- | 200 | 225 | 155 | 175 |
4/0 | --- | 230 | 260 | 180 | 205 |
250 | --- | 255 | 290 | 205 | 230 |
300 | --- | 285 | 320 | 230 | 260 |
350 | --- | 310 | 350 | 250 | 280 |
500 | --- | 380 | 430 | 310 | 350 |
600 | --- | 420 | 475 | 340 | 385 |
750 | --- | 475 | 535 | 385 | 435 |
1000 | --- | 545 | 615 | 445 | 500 |
Amp or AMP may refer to: Ampere, a unit of electric current, often shortened to amp. Pixatool 1 54 – create 8bit pixel style images ideas. This page was last edited on 15 October 2020, at 22:28 (UTC). 2 times the power (−3) dB ≡ damping to the value 0.5 6 dB ≡ 4 times the power (−6) dB ≡ damping to the value 0.25: 10 dB ≡ 10 times the power (−10) dB ≡ damping to the value 0.1: 12 dB ≡ 16 times the power (−12) dB ≡ damping to the value 0.0625 20 dB ≡ 100 times the power. 15 AMP 2 pole 2 wire 2 pole 3 wire grounding 3 pole 3 wire 3 pole 4 wire grounding 4 wire; 125V 250V 125V 250V 277V 125/250V 250V 125/250V 250V 120/ 208V; Receptacle. Tower Manufacturing Shock Buster 15-Amp 125-Volt General-Duty NEMA 5-15p Straight Plug. Model #30334203. Compare; Find My Store. 1,763 6am to 2pm jobs available on Indeed.com. Apply to Warehouse Worker, Client Services Associate, Server and more!
WARNING! Installation of electrical wire can be hazardous and, if done improperly can result in personal injury or property damage. For safe wiring practices, consult the National Electrical Code®, your local building inspector, or a qualified electrician.
Ampacities are based on the 2017 NEC and do not reflect any temperature correction or ampacity adjustments that may be required. Please consult a qualified electrician or professional engineer to determine the appropriate values for your specific application.